Battery Charger-Analyzer for small battery systems (up to 10A-Hr)
(replaces the earlier 24-400T)

  • The 24-400XG is an instrument designed to charge, trickle charge and analyze (discharge) Nickel-Cadmium, Sealed Lead-Acid and other types of rechargeable batteries.

The 24-400XG is an instrument designed to charge, trickle charge and analyze (discharge) Nickel-Cadmium, Sealed Lead-Acid and other types of rechargeable batteries.

With its multiple modes of operation of Constant Current Charge (dual and single rate), Constant Current & Float Charge, Constant Current & Peak Stop Charge, Automatic Discharge (analysis), Resistance Discharge (analysis) and Full Discharge (deep cycle), the 24-400XG can satisfy the requirements of most small (0 to 10 A-hr) rechargeable battery systems.

The instrument features safety interlocks to protect the operator, the charger and the battery in the event of reversed polarity connection, short circuit, open circuit (no load) and Overvoltage conditions.

Two large LED digital meters permit the simultaneous monitoring of voltage and current, while eight indicator lights inform of the status of the operation.

Storage (nonvolatile) of battery test profiles

Battery temperature monitoring

Microprocessor based timer with HH:MM and MM:SS timing selection

Interfacing to the BTAS16 Computerized Battery Test System for monitoring, programming and control

Suggested Accessory: we recommend the CAL-100 to simplify the task of testing and calibration the Charger-Analyzer.

 

SPECIFICATIONS 

CURRENT
Charge: constant current, adjustable: 0 to 1.999A, in steps of 1mA (0.002A).
Discharge: constant current, adjustable: 0 to 10.00A, in steps of 10mA (0.01A).

VOLTAGE
Charge: 0 to 40V.
Discharge: 3 to 24V at full current, and up to 44V at reduced current (240W max power dissipation).

MODES
Constant Current Charge
    Single Rate
    Single Rate with stop at peak voltage

    Dual Rate
    Dual Rate with transfer at peak voltage
    (all with optional Overvoltage)
Constant Voltage Charge.
   
Constant Current followed by Constant Voltage
Discharge
    Constant Current Capacity Test
    Constant Resistance Load Capacity Test
    Full Discharge

VOLTAGE CONTROL
Adjustable: Usable from 3.00 to 44.0V, with an accuracy of 2% ±.1V

METERS
Voltage: 3-1/2 digit, LED digital panel meter, 0 to 19.99 and 199.9V scales.    
Current: 3-1/2 digit, LED digital panel meter, 0 to 1.999A scale for charge and 0 to 19.99A scale for discharge.  

CONTROLS
24 button keypad to select the Test Mode, program the Test Parameters and view status and results.

DISPLAY
24 button keypad to select the Test Mode, program the Test Parameters and view status and results.

STATUS INDICATORS
RESET and CYCLE END.
MAIN and TOPPING CHARGE.
DISCHARGE.
PEAK VOLTAGE END.
CAPACITY FAILURE END.
WARNING and FAULT

TIMER
Microprocessor controlled with HH:MM, MM:SS elapsed time selection.

PROTECTION
Battery Overtemp
    Battery Temperature monitoring by way of an external cable or Temp-Plate
Overheat
    Monitoring of internal Heat Dissipators
Power Failure
    Internal rechargeable battery.
Current
    Microprocessor monitored for over and under current faults
    Fusing for Line,
Charge output and Discharge output.

LINE VOLTAGE
115/230VAC ±10%, 50-60Hz.

AMBIENT
+5oC to +35oC (contact factory for extended temperature operation).

PART NUMBER
9891601011

APPROVALS
TBA

MANUAL

Note: Specifications subject to change without notice

 


[Home] [Articles] [Batteries] [Brochures] [Contact us] [Credit card orders] [Español] [FAQs] [Gallery] [Links] [Manuals] [Parts] [Products] [Services]
[Technical Bulletins] [Technical Notes] [Trade-in] [Upgrades] [Who we are] 
Send mail to webmaster@jfmeng.com with questions or comments about this web site.
Copyright © 2012 JFM Engineering, Inc. --- Last modified: January 09, 2012