JFM Engineering, Inc. - Miami, Florida, USA


 

Supersederxg
Battery Charger-Analyzer for large battery systems (10A-hr to 100A-hr)
(advanced version of the earlier Superseder III)

 

  • The 24-400XG is an instrument designed to charge, trickle charge and analyze (discharge) Nickel-Cadmium, Sealed Lead-Acid and other types of rechargeable batteries.

The SupersederXG is an instrument designed to charge, trickle charge and analyze (discharge) Nickel-Cadmium, Sealed Lead-Acid and other types of rechargeable batteries.

With its multiple modes of operation of Constant Current Charge (dual and single rate), Constant Current & Float Charge, Constant Current & Peak Stop Charge, Automatic Discharge (analysis), Resistance Discharge (analysis) and Full Discharge (deep cycle), the SupersederXG can satisfy the requirements of most large (10 A-hr to 100A-hr) rechargeable battery systems.

The instrument features safety interlocks to protect the operator, the charger and the battery in the event of reversed polarity connection, short circuit, open circuit (no load) and Overvoltage conditions.

Two large LED digital meters permit the simultaneous monitoring of voltage and current, while eight indicator lights inform of the status of the operation.

Storage (nonvolatile) of battery test profiles

Battery temperature monitoring

Microprocessor based timer with HH:MM and MM:SS timing selection

Interfacing to the BTAS16 Computerized Battery Test System for monitoring, programming and control

 

SPECIFICATIONS 

CURRENT
Charge: constant current, programmable: 0 to 50.0A, in steps of 0.1A.
Discharge: constant current, programmable: 0 to 60.0A, in steps of 0.1A.

VOLTAGE
Charge: 0 to 77V
Discharge: 3 to 24V at full current, and up to 48V at reduced current (power dissipation limited).

MODES
Constant Current Charge
    Single Rate
    Single Rate with stop at peak voltage

    Dual Rate
    Dual Rate with transfer at peak voltage
    (all with optional Overvoltage)
Constant Voltage Charge.
   
Constant Current followed by Constant Voltage
Discharge
    Constant Current Capacity Test
    Constant Resistance Load Capacity Test
    Full Discharge

VOLTAGE CONTROL
Adjustable: Usable from 3.00 to 80.0V, with an accuracy of 2% ± 0.1V

METERS
Voltage: 3-1/2 digit, LED digital panel meter, 0 to 19.99V and 199.9V scales.    
Current: 3-1/2 digit, LED digital panel meter, 0 to 199.9A scale for charge and discharge.  

CONTROLS
24 button keypad to select the Test Mode, program the Test Parameters and view status and results.

DISPLAY
LCD readout with 4 lines x 20 characters.

STATUS INDICATORS
RESET and CYCLE END.
MAIN and TOPPING CHARGE.
DISCHARGE.
PEAK VOLTAGE END.
CAPACITY FAILURE END.
WARNING and FAULT

TIMER
Microprocessor controlled with HH:MM and MM:SS elapsed time selection.

PROTECTION
Battery Overtemp
    Battery Temperature monitoring by way of an external cable or Temp-Plate
Overheat
    Monitoring of internal Heat Dissipators
Power Failure
    Internal rechargeable battery.
Current
    Microprocessor monitored for over and under current faults
    Fusing for Line,
Charge output and Discharge output.

LINE VOLTAGE
115VAC (limited charge capability) / 208,230,245VAC ±10%, 50-60Hz.

AMBIENT
+5oC to +35oC (contact factory for extended temperature operation).

PART NUMBER
9899603011

APPROVALS
TBA

ACCESSORIES
TEMP-PLATE: Plate to measure the temperature of the battery(ies)
SINGLE CELL ADAPTOR: Short cable with clips to charge a single cell or a group of cells

MANUAL

Note: Specifications subject to change without notice

 


[Home] [Articles] [Batteries] [Brochures] [Contact us] [Credit card orders] [Español] [FAQs] [Gallery] [Links] [Manuals] [Parts] [Products] [Services]
[Technical Bulletins] [Technical Notes] [Trade-in] [Upgrades] [Who we are] 
Send mail to webmaster@jfmeng.com with questions or comments about this web site.
Copyright © 2012 JFM Engineering, Inc. --- Last modified: January 09, 2012